Use this table to calculate the cooling capacity you need in a portable air conditioner for your server room or computer room.

Area to Be Cooled
(sq.ft.)
Capacity
(Btu/Hr)
100 to 150 5,000
150 to 250 6,000
250 to 300 7,000
300 to 350 8,000
350 to 400 9,000
400 to 450 10,000
450 to 550 12,000
500 to 700 14,000
700 to 1000 18,000
Please note:

If the room is heavily shaded, reduce capacity by 10%.
If the room is very sunny, increase capacity by 10%.
If more than two people regularly occupy the room, add 600 Btu/Hr for each additional person.
If the unit is for a kitchen, increase capacity by 4,000 Btu/Hr.
For each server add 1200-1500 BTU's.
For each UPS add 800-1000 BTU's.

Cooling can be a factor of heat, space, and amount of heat generating equipment in a room. Cooling is expressed in BTU's or British Thermal Units. Air conditioning equipment is usually expressed in tons, i.e., a one ton air conditioner. One ton of air conditioning is equal to 12,000 BTU's.

Provided for informational purposes only, and results are not to be construed other than as recommendations.

A room that is 10' x 10' x 8' is 800 cubic feet. 800 cubic feet multiplied by a factor of 5 cubic feet for computers, servers, etc., equals 4,000 BTU's.

For a more accurate picture of your room, please contact us.